Why an Open Transmission Line End Sees Double Voltage Under a Travelling Wave
When a breaker closes onto a long transmission line, a voltage step travels along the conductor rather than appearing everywhere at once. The wave's speed and surge impedance depend only on the line's inductance and capacitance per unit length, not its total length. In a worked 100 km example, the one-way travel time is about a third of a millisecond. The far-end termination determines the outcome: an open end reflects the wave fully and doubles the voltage, a shorted end drives it to zero, and a load matched to the surge impedance produces no reflection at all. Partial mismatches produce smaller, decaying reflections that bounce between the ends until the system settles.