Why a 16 A AC switch is not rated 16 A on DC circuits
A 16 A 250 V AC rocker switch cannot be assumed to carry 16 A on DC because the AC current crosses zero roughly 100 to 120 times per second, extinguishing contact arcs quickly. On DC there is no zero crossing, so arcs persist until the gap exceeds the supply voltage, causing much faster contact erosion. A part rated 16 A at 250 V AC may be limited to about 10 A at 30 V DC and considerably less at 110 V DC, if it has a DC rating at all. Risks arise in 12, 24 and 48 V battery or solar circuits, DC motor reversing and inductive DC coils, and remedies include DC-rated switches with magnetic blowout, contactors, or appropriately sized snubbers. The source notes these figures come from a manufacturer rather than an independent test report.